FAQ No. FAQ00258
Question
Using CX-Programmer, how can we connect PLC
via Ethernet?
Answer
1. Personal Computer Ethernet setting by IP Address and Subnet Mask.
2. Ethernet Unit: IP Address, Node No., Unit No.
3. CX-Programmer and CS1 Programmable Controller is connected with Tool
bus Cable.
4. CX-Programmer I/O table Window: Unit Setting (CPU bus unit System
Setting) is required to be set for Ethernet [IP Address Conversion] by
Automatic generation, [Sub net mask] is set.
5. CX-Programmer (CX-Net): FINS Local Routing table is created and
transferred to CS1.
6. Personal Computer issues PING Command to check if Ethernet connection
is OK.
7. CX-Programmer Communication Setting
Personal Computer Model Change / [Network
Type] is set [Ethernet].
Click [Setting], set FINS destination
address [Network] / [Node]
(Node = Ethernet Unit Node Number, Network = Network address set in
Routing table)
Check Automatic generation method at
[Driver] tab / Workstation node Address. Port Number = 9600.