Programmable Controller Topic: Connect PLC via Ethernet Using CX-Programmer

 

FAQ No. FAQ00258

 

Question

Using CX-Programmer, how can we connect PLC via Ethernet?



Answer

1. Personal Computer Ethernet setting by IP Address and Subnet Mask.
2. Ethernet Unit: IP Address, Node No., Unit No.
3. CX-Programmer and CS1 Programmable Controller is connected with Tool bus Cable.
4. CX-Programmer I/O table Window: Unit Setting (CPU bus unit System Setting) is required to be set for Ethernet [IP Address Conversion] by Automatic generation, [Sub net mask] is set.
5. CX-Programmer (CX-Net): FINS Local Routing table is created and transferred to CS1.
6. Personal Computer issues PING Command to check if Ethernet connection is OK.
7. CX-Programmer Communication Setting

  1. Personal Computer Model Change / [Network Type] is set [Ethernet].

  2. Click [Setting], set FINS destination address [Network] / [Node]
    (Node = Ethernet Unit Node Number, Network = Network address set in Routing table)

  3. Check Automatic generation method at [Driver] tab / Workstation node Address. Port Number = 9600.

 

 