Digital Panel Meter Topic: BCD Output

 

FAQ No. FAQ00763

 

Question

The BCD output is not being output from a Meter with a BCD output. What should I do?


Answer

 

Is the REQ terminal open? Check the connections again.
With the K3N[] Series, the BCD output data is output when an external REQ signal is received.

(1) When a large Display Unit that accepts BCD inputs (such as an M7E) is connected, securely connect the REQ terminal and COM terminal.

Example Connection to a Display Unit:

 

Example Connection to a Display Unit

 


2) When connecting to a PLC, create a ladder program that outputs an REQ signal from the PLC and scans for data when the D.V. (Data Valid) signal goes from OFF to ON.

Example Connection to a Programmable Controller:

 

Example Connection to a Programmable Controller

 

Reference Information

• Timing Chart for BCD Outputs
(A Request signal from an external device (such as a PLC) is required to read the BCD data.)

(1) One Sample of Data Output

 

One Sample of Data Output

 

About 30 ms after the REQ signal goes ON, the data is set and the Data Valid signal is output. When reading the data with a Programmable Controller, wait until the Data Valid signal turns ON and then read the data. The Data Valid signal will turn OFF after 40 ms and then the data will turn OFF 16 ms after the Data Valid signal.

 

(2) Continuous Data Output

 

Continuous Data Output

If the REQ signal remains ON, the measured data will be output every 64 ms.

Note: If the HOLD input is used when the data switches from Data 1 to Data 2, either Data 1 or Data 2 will be output as the BCD data, depending on the timing of the HOLD signal. The data signals will not be set to LOW.

 

 