Frequently Asked Questions

Power Supply Topic: Size Load to Connect to S82J / S82K Model

 

FAQ No. FAQ02007

 

Question

What size load (as a percentage of Power Supplies' rated output capacity) can be connected to S82J or S82K Series Switch Mode Power Supply?



Answer

 

Generally speaking, it is possible to connect a load up to 100% of the rated output capacity (see note), but there are drawbacks. When Power Supplies are operated near their rated output capacity, inrush currents and load variations may trigger the overcurrent protection function, causing the output to stop and reducing the lifetime of Power Supplies. We recommend normal operation at about 70% to 80% of the rated capacity.

Note: There are cases when it is not possible to connect a load up to 100% of the rated capacity (for example, when the Power Supply is being used in parallel operation).

 

 

Other Power Supply FAQs

 Are there models available that support parallel operation?

 The output indicator turns ON, but then turns OFF immediately. What is the cause of the problem and solution (in models equipped with the overvoltage protection function)?