FAQ No. FAQ02034
Question
For G3PX Power Controller with the constant-current function,
can protection be provided with the G3PX against load short circuiting?
Answer
No. Protection is not provided.
If short-circuit current flows, the elements will be destroyed before the
constant-current or overcurrent detection currents operate. To protect the
G3PX from short-circuit accidents, connect a quick-burning fuse.
Recommended fuses
|
Model Number |
Manufacture |
|
Product |
Fuse |
|
G3PX-220[][][] |
50SHA20
60PFF20 |
Kyosan Electric Mfg. Co.
Ltd. |
|
G3PX-240[][][] |
50SHA40 |
|
G3PX-260[][][] |
URD-30063 |
FERRAZ
SHAWMUT
JAPAN INC. |

Other Power Controller
FAQs
Can three G3PX Controllers for single-phase applications be combined for control of three-phase loads?
Which terminals should the G3PX inputs be connected to?
What is a soft start?
|