Interface Converter
            
        
* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.
last update: August 5, 2015
| Item | K3SC-10 100 to 240 VAC | K3SC-10 24 VAC/VDC | |
|---|---|---|---|
| Supply voltage | 100 to 240 VAC 50/60 Hz | 24 VAC 50/60 Hz, 24 VDC | |
| Operating voltage range | 85% to 110% of power supply voltage | ||
| Power consumption | 5 VA max. | 3 VA max./3 W max. | |
| 
										Master/slave device communications format (Select one of the formats listed on the right using the DIP switch.)  | 
									Master Device ↔ Slave Device RS-232C or USB ↔ RS-485, half duplex RS-232C or USB ↔ RS-422, full duplex USB ↔ RS-232C, full duplex  | 
								||
| Communications method | Start-stop synchronization | ||
| Ambient operating temperature | RS-232C | -10 to 55 °C (with no icing) | |
| USB | 0 to 55 °C (with no icing) | ||
| Ambient operating humidity | 25% to 85% (with no condensation) | ||
| Ambient storage temperature | -20 to 65 °C | ||
| Item | Specification | |||
|---|---|---|---|---|
| Master
 device  | 
									RS-232C
 interface (See note 1.)  | 
									Maximum transmis-
 sion distance  | 
									15 m | |
| Maximum number of
 connectable Units  | 
									1 Unit | |||
| USB
 interface (See note 2.)  | 
									Maximum transmis-
 sion distance  | 
									5 m; hub delay time + cable delay time ≤ 70 ns | ||
| Maximum number of
 connectable Units  | 
									1 Unit | |||
| USB standard | V1.1 | |||
| Slave
 device  | 
									RS-485
 interface  | 
									Maximum transmis-
 sion distance  | 
									500 m | |
| Maximum number of
 connectable Units  | 
									31 Units (for multi-drop connection) | |||
| RS-422
 interface  | 
									Maximum transmis-
 sion distance  | 
									500 m | ||
| Maximum number of
 connectable Units  | 
									1 Unit | |||
| Baud rate | 1,200/2,400/4,800/9,600/19,200/38,400 (bps)
 Default setting: 9,600  | 
								|||
| Data length | 7/8 bits
 Default setting: 7  | 
								|||
| Stop bit length | 1/2 bits
 Default setting: 2  | 
								|||
| Communications parity | None/even/odd
 Default setting: Even  | 
								|||
| Echoback selection | Echoback: With/without
 Default setting: Without  | 
								|||
| Selection switch response delay | Approx. 30 ms | |||
| Insulation resistance | 20 MΩ min. measured at 500 VDC between the following:
 External terminals ↔ casing RS-232C terminals and USB port ↔ RS-422/485 terminals ↔ power supply terminals  | 
								|||
| Isolation
 method  | 
									Commu-
 nications  | 
									Phototransistor coupler | ||
| Power
 supply  | 
									Isolating transformer | |||
| Dielectric strength | 1,500 VAC for 1 minute measured between the following:
 External terminals ↔ casing RS-232C terminals, USB port, RS-422 terminals, and RS-485 terminals ↔ power supply terminals  | 
								|||
| 500 VAC for 1 minute measured between the following:
 RS-232C terminals and USB port ↔ RS-422 terminals and RS-485 terminals  | 
								||||
| Noise immunity | AC power supply terminals, normal/common mode: ±1,500 V
 AC/DC power supply terminals, normal mode: ±480 V; common mode: ±1,500 V Square wave with 1-ns rising edge ±1 μs, ±100 ns  | 
								|||
| Vibration
 resistance  | 
									Malfunction | 10 to 55 Hz, 0.5-mm single amplitude for 10 minutes each in X, Y, and Z directions | ||
| Destruction | 10 to 55 Hz, 0.75-mm single amplitude for 2 hours each in X, Y, and Z directions | |||
| Shock resistance | Malfunction | 98 m/s2 3 times each in X, Y, and Z directions | ||
| Destruction | 294 m/s2 3 times each in X, Y, and Z directions | |||
| Weight | Approx. 150 g | |||
| Degree of protection
 (See note 3.)  | 
									Front panel
 operation parts  | 
									Conforms to IEC standards, equivalent to IP20 (when terminal cover mounted) | ||
| Terminals | Equivalent to VDE 0106/100 (when terminal cover mounted) | |||
| EMC | (EMI) EN61326-1 Industrial electromagnetic environment
 Emission Enclosure: CISPR 11 Group 1 class A: CISRP16-1/-2 Emission AC Mains: CISPR 11 Group 1 class A: CISRP16-1/-2 (EMS) EN61326-1 Industrial electromagnetic environment Immunity ESD: EN61000-4-2: 4 kV contact discharge (level 2), 8 kV air discharge (level 3) Immunity RF-interference: EN61000-4-3: 10 V/m (amplitude-modulated, 80 MHz to 1 GHz) (level 3) Immunity Fast Transient Noise: EN61000-4-4: 2 kV (power line) (level 3) Immunity Burst Noise: 1 kV line to line (I/O signal line) Immunity Surge: EN61000-4-5: 1 kV line to line, 2 kV line to ground (power line) Immunity Conducted Disturbance EN61000-4-6: 3 V (0.15 to 80 MHz) (level 2) Immunity Voltage Dip/Interrupting EN61000-4-11: 0.5 cycles, 0, 180°, 100% (rated voltage)  | 
								|||
| Approved standards | UL508, Conforms to EN61326-1, EN61010-1 (IEC61010-1) | |||
| Memory protection | No protective functions (Communications data is not protected for power interruptions
 during communications.)  | 
								|||
last update: August 5, 2015