Industrial Automation|

New Zealand

Clearance Centre

Sitemap

Contact

OMRON IA Global

 
Selection Guide

Main :: Automation Systems :: CompoNet

CompoNet Selection Guide

CompoNet Master Units

 

Name

Appearance

Specifications

Number of
unit numbers
allocated

Power consumption (A)

5 V system

Model

Standards

Types of communications

Maximum number of I/O points per Master Unit

CS1 Special I/O Unit *

CS1W-CRM21

• Remote I/O communications

• Message communications

Word Slave Units: 1,024 inputs and 1,024 outputs (2,048 I/O points total)


Bit Slave Units: 256 inputs and 256 outputs (512 I/O points total)

1, 2, 4 or 8

0.4

CS1W-CRM21

CE, UL, UL (Class I Div2), LR, NK

CJ1 Special I/O Unit *

CJ1W-CRM21

• Remote I/O communications

• Message communications

Word Slave Units: 1,024 inputs and 1,024 outputs (2,048 I/O points total)


Bit Slave Units: 256 inputs and 256 outputs (512 I/O points total)

1, 2, 4 or 8

0.4

CJ1W-CRM21

CE, UL (Class I Div2), LR, NK

 

* These Units are also available with a DCN-TB4 Terminal Conversion Adapter included in the package. Add "(-B)" to the end of the model number to receive the Adapter as well.

 

CompoNet Master Boards

 

Name

Appearance

Specifications

Model

Standards

PCI Bus type

388F7-CRM21

PCI bus Rev2.2 5V

3G8F7-CRM21

CE

CompactPCI
Bus type

388F8-CRM21

PICMG 2.0 R3.0 5V 32-Bit 3U

3G8F8-CRM21

 

 

CompoNet Slave Units

 

Word Slave Units

 

• Digital I/O Slave Units

 

 Name

Appearance

Specifications

Communications Cables

Model

Standards

Round Cable I Round Cable II Standard Flat Cable I Sheathed Flat Cable II

Two tier Screw Terminal Block

Two-tier Screw Terminal Block

Inputs

8 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-ID08

CE, UL, UL (Class I Div2), NK

PNP

CRT1-ID08-1

Outputs

8 outputs

NPN

CRT1-OD08

PNP

CRT1-OD08-1

Inputs

16 inputs

NPN

CRT1-ID16 *

CE, UL, UL (Class I Div2), CSA, NK

PNP

CRT1-ID16-1 *

Outputs

16 outputs

NPN

CRT1-OD16 *

PNP

CRT1-OD16-1 *

Inputs/ Outputs

8 inputs/ 8 outputs

NPN

CRT1-MD16

CE, UL, UL (Class I Div2), NK

PNP

CRT1-MD16-1

Screw Terminal Block with Relay Outputs

Screw Terminal Block with Relay Outputs

Outputs

8 outputs

Contacts

Yes

Yes

Yes

Yes

CRT1-ROS08

CE, cULus, cULus (Class I Dis2), NK

16 outputs

CRT1-ROS16

Screw Terminal Block with SSR Outputs

Outputs

8 outputs

SSR

CRT1-ROF08

--

16 outputs

CRT1-ROF16

Three-tier Screw Terminal Block

 

(Without Short-circuit and Disconnected Line Detection)

Three-tier Screw Terminal Block

Inputs

8 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-ID08TA

CE, cULus, cULus (Class I Dis2)

PNP

CRT1-ID08TA-1

Outputs

8 outputs

NPN

CRT1-OD08TA

PNP

CRT1-OD08TA-1

Inputs

16 inputs

NPN

CRT1-ID16TA

PNP

CRT1-ID16TA-1

Outputs

16 outputs

NPN

CRT1-OD16TA

PNP

CRT1-OD16TA-1

Inputs/ outputs

8 inputs and 8 outputs

NPN

CRT1-MD16TA

PNP

CRT1-MD16TA-1

Three-tier Screw Terminal Block

 

(With Short-circuit and Disconnected Line Detection)

Inputs

8 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-ID08TAH

PNP

CRT1-ID08TAH-1

Outputs

8 outputs

NPN

CRT1-OD08TAH

PNP

CRT1-OD08TAH-1

Inputs

16 inputs

NPN

CRT1-ID16TAH

PNP

CRT1-ID16TAH-1

Outputs

16 outputs

NPN

CRT1-OD16TAH

PNP

CRT1-OD16TAH-1

Inputs/ outputs

8 inputs and 8 outputs

NPN

CRT1-MD16TAH

PNP

CRT1-MD16TAH-1

e-CON Connectors

 

 

(Without Short-circuit and Disconnected Line Detection)

Digital I/O Slave Units with Connectors

Inputs

16 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-ID16S

CE, cULus, cULus (Class I Dis2)

PNP

CRT1-ID16S-1

Outputs

16 outputs

NPN

CRT1-OD16S

PNP

CRT1-OD16S-1

Inputs/ outputs

8 inputs and 8 outputs

NPN

CRT1-MD16S

PNP

CRT1-MD16S-1

Inputs

32 inputs

NPN

CRT1-ID32S

PNP

CRT1-ID32S-1

Outputs

32 outputs

NPN

CRT1-OD32S

PNP

CRT1-OD32S-1

Inputs/ outputs

16 inputs and 16 outputs

NPN

CRT1-MD32S

PNP

CRT1-MD32S-1

e-CON Connectors

 

 

(With Short-circuit and Disconnected Line Detection)

Digital I/O Slave Units with Connectors

Inputs

16 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-ID16SH

PNP

CRT1-ID16SH-1

Outputs

16 outputs

NPN

CRT1-OD16SH

PNP

CRT1-OD16SH-1

Inputs/ outputs

8 inputs and 8 outputs

NPN

CRT1-MD16SH

PNP

CRT1-MD16SH-1

Inputs

32 inputs

NPN

CRT1-ID32SH

PNP

CRT1-ID32SH-1

Outputs

32 outputs

NPN

CRT1-OD32SH

PNP

CRT1-OD32SH-1

Inputs/ outputs

16 inputs and 16 outputs

NPN

CRT1-MD32SH

PNP

CRT1-MD32SH-1

e-CON Connectors*

 

(Without Short-circuit and Disconnected Line Detection)

Digital I/O Slave Units with e-CON Connectors

Inputs

8 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-VID08S

PNP

CRT1-VID08S-1

Outputs

8 outputs

NPN

CRT1-VOD08S

PNP

CRT1-VOD08S-1

MIL Connectors *

CompoNet Digital I/O Slaves with MIL Connectors

Inputs

16 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-VID16ML

CE, cULus, cULus (Class I Dis2), NK

PNP

CRT1-VID16ML-1

Outputs

16 outputs

NPN

CRT1-VOD16ML

PNP

CRT1-VOD16ML-1

MIL Connectors *

CompoNet Digital I/O Slaves with MIL Connectors

Inputs

32 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-VID32ML

CE, cULus, cULus (Class I Dis2), NK

PNP

CRT1-VID32ML-1

Outputs

32 outputs

NPN

CRT1-VOD32ML

PNP

CRT1-VOD32ML-1

Inputs/ outputs

16 inputs and 16 outputs

NPN

CRT1-VMD32ML

PNP

CRT1-VMD32ML-1

Clamp Terminal Blocks

CompoNet Digital I/O Slaves with Clamp Terminals

Inputs

8 inputs

NPN

Yes

Yes

Yes

Yes

CRT1-ID08SL

CE, NK

PNP

CRT1-ID08SL-1

Outputs

8 outputs

NPN

CRT1-OD08SL

PNP

CRT1-OD08SL-1

Inputs

16 inputs

NPN

CRT1-ID16SL

PNP

CRT1-ID16SL-1

Outputs

16 outputs

NPN

CRT1-OD16SL

PNP

CRT1-OD16SL-1

Inputs/ outputs

8 inputs and 8 outputs

NPN

CRT1-MD16SL

PNP

CRT1-MD16SL-1

 

* These Units are also available with a DCN-TB4 Terminal Conversion Adapter included in the package. Add "(-B)" to the end of the model number to receive the Adapter as well.

 

 

• Analog I/O Slave Units

 

 Name

Appearance

Specifications

Communications Cables

Model

Standards

Round Cable I Round Cable II Standard Flat Cable I Sheathed Flat Cable II

Analog I/O Slave Units *

Analog I/O Slave Units

Analog Inputs

4 inputs

Yes

Yes

Yes

Yes

CRT1-AD04

CE, UL, UL (Class 1 Div2), CSA, NK

Analog outputs

2 outputs

CRT1-DA02

MIL Connector Type

Analog I/O Slave Units (MIL Connector Type)

Analog Inputs

4 inputs

CRT1-VAD04ML

CE, cULus, cULus (Class I Dis2)

Analog outputs

2 outputs

CRT1-VDA02ML

e-CON Connector Type

Analog I/O Slave Units (e-CON Connector Type)

Analog Inputs

4 inputs

CRT1-VAD04S

Analog outputs

2 outputs

CRT1-VDA02S

Numerical Indicator,

MIL Connector Type

Analog I/O Slave Units (Numerical Indicator, MIL Connector Type)

Analog inputs (Channel Insulation)

2 inputs

Yes

Yes

Yes

Yes

CRT1-VAD02MLD

CE

 

Analog outputs

2 outputs

CRT1-VDA02MLD

Numerical Indicator,

e-CON Connector Type

Analog I/O Slave Units (Numerical Indicator, e-CON Connector Type)

Analog inputs (Channel Insulation)

2 inputs

CRT1-VAD02SD

Analog outputs

2 outputs

CRT1-VDA02SD

 

* These Units are also available with a DCN-TB4 Terminal Conversion Adapter included in the package. Add "(-B)" to the end of the model number to receive the Adapter as well.

 

 

• Temperature Input Units

 

 Name

Appearance

Specifications

Communications Cable

Model

Standards

Round Cable I Round Cable II Standard Flat Cable I Sheathed Flat Cable II

Temperature Input Units

Temperature Input Units

Thermocouple Input

4 inputs

Switchable between (R, S, K, J, T, E, B, N, L, U, W, PL2)

Yes

Yes Yes Yes

CRT1-TS04T

CE, cULus, cULus (Class I Dis2), NK

Platinum- resistance thermometer input

PT100 (-200 to 850°C)
PT100 (-200 to 2000°C)

CRT1-TS04P

 

 

• Expansion Units

 

 Name

Appearance

Specifications

Model

Standards

Expansion Units

Expansion Units

Inputs

8 inputs

NPN

One Expansion Unit can be mounted to one CRT1-ID16(-1), CRT1-OD16(-1), CRT1-ROS16, or CRT1-ROF16 Digital I/O Slave.

XWT-ID08

CE, cULus, cULus (Class I Dis2), NK

PNP

XWT-ID08-1

Outputs

8 outputs

NPN

XWT-OD08

PNP

XWT-OD08-1

Inputs

16 inputs

NPN

XWT-ID16

PNP

XWT-ID16-1

Outputs

16 outputs

NPN

XWT-OD16

PNP

XWT-OD16-1

Expansion Units e-CON Connector type

---

Digital outputs

8 outputs

NPN

One Expansion Unit can be mounted to one CRT1-VAD02[][]D or CRT1-VDA02[][]D Analog I/O Slave Unit.

XWT-VOD08S

---

Digital outputs

8 outputs

PNP

XWT-VOD08S-1

Digital inputs & outputs

4 inputs/

4 outputs

NPN

XWT-VMD08S

Digital inputs & outputs

4 inputs/

4 outputs

PNP

XWT-VMD08S-1

Expansion Units MIL Connector type ---

Digital outputs

16 inputs

NPN

XWT-VOD16ML

Digital outputs

16 inputs

PNP

XWT-VOD16ML-1

Digital inputs & outputs

8 inputs/

8 outputs

NPN

XWT-VMD16ML

Digital inputs & outputs

8 inputs/

8 outputs

PNP

XWT-VMD16ML-1

 

 

Bit Slave Units

 

• Compact Connectors

 

 Name

Appearance

Specifications

Communications Cables

Model

Standards

Round Cable I Round Cable II Standard Flat Cable I Sheathed Flat Cable II

Compact Connectors

Compact Connectors

Inputs

2 inputs

NPN

Yes

Yes

Yes

Yes

CRT1B-ID02JS

CE

2 outputs

PNP

CRT1B-ID02JS-1

Outputs

2 inputs

NPN

CRT1B-OD02JS

2 outputs

PNP

CRT1B-OD02JS-1

Inputs/ Outputs

1 input/

1 output

NPN

CRT1B-MD02JS

1 input/

1 output

PNP

CRT1B-MD02JS-1

Compact Connectors

Inputs

4 inputs

NPN

CRT1B-ID04JS

4 outputs

PNP

CRT1B-ID04JS-1

Outputs

4 inputs

NPN

CRT1B-OD04JS

4 outputs

PNP

CRT1B-OD04JS-1

Inputs/ Outputs

2 inputs/ 2 outputs

NPN

CRT1B-MD04JS

2 inputs/ 2 outputs

PNP

CRT1B-MD04JS-1

IP20

IP20

Inputs

2 inputs

NPN

No

No

Yes

No

CRT1B-ID02S

CE, UL

PNP

CRT1B-ID02S-1

Outputs

2 outputs

NPN

CRT1B-OD02S

PNP

CRT1B-OD02S-1

 

 

• Repeater Unit

 

 Name

Appearance

Specifications

Communications Cables

Model

Standards

Round Cable I Round Cable II Standard Flat Cable I Sheathed Flat Cable II

Repeater Unit *

Repeater Unit

A sub-trunk line can be connected downstream (for trunk-branch line configuration) or further branching is enabled downstream (for configurations with no wiring restrictions) in the same way as for a Master Unit. A Repeater Unit can be used to branch the trunk line and increase the number of connected Units, as well as to extend the length of the communications line.

Yes

Yes

Yes

Yes

CRS1-RPT01

CE, UL, UL (Class I Div2), LR, NK

 

* These Units are also available with a DCN-TB4 Terminal Conversion Adapter included in the package. Add "(-B)" to the end of the model number to receive the Adapter as well.

 

 

• SmartSlice GRT1 Series: CompoNet Communications Unit

 

 Name

Appearance

Specifications

Model

Standards

CompoNet Communications Unit

CompoNet Communications Unit

Up to 64 Slice I/O Units can be connected
(Inputs: 32 bytes maximum, Output: 32 bytes maximum)

GRT1-CRT

CE, cULus (Class I Dis2), Lloyd

 

 

• Sensor Communications Unit

 

 Name

Appearance

I/O classification

Allocated bits Internal circuit power supply I/O power supply voltage

Connected Controller model

Model

Standards

Sensor Communications Unit

Sensor Communications Unit

Input and output

160 bits max.

Supplied along with communications power

24 VDC

ZS-LDC[][]
ZS-MDC[][]
ZS-HLDC[][]
ZFV-CA[][]
ZG-WDC[][]

ZS-CRT

CE

 

 

 

 

 


 

 

CompoNet Slave Unit Functions

 

The Slave Units provide Smart Functions that powerfully aid in everything from building the system and initial system startup to preventive system maintenance. The Smart Functions include functions for monitoring the operation time, changes in operating values, and other values, as well as functions that provide warnings for maintenance based on ON/OFF counts, total operating time, and other counted values.

 

 

Yes: Supported, ---: Not supported

 

Function

Digital I/O Slave Units

2-tier Terminal block

CRT1-[]D08(-1)

CRT1-[]D16(-1)

CRT1-ROS08

CRT1-ROS16

CRT1-ROF08

CRT1-ROF16

Input Units

Output Units

Input Units

Output Units

I/O Units

Output Units

Output Units

Operation Time Monitor

Yes

Contact Operation Monitor (See note.)

Yes

Total ON Time Monitor (See note.)

Yes

Automatic Baud Rate Detection

Yes

Unit Conduction Time Monitor

Yes

Naming Units

Yes

Naming Connected Devices

Yes

Network Power Voltage Monitor

Yes

I/O Power Status Monitor

Yes

---

Communications Error History Monitor

Yes

Input Filter

Yes

---

Yes

---

Yes

---

Communications Error Output

---

Yes

---

Yes

Yes

Yes

Preventing Malfunctions Caused by Inrush Current at I/O Startup

Yes

---

Yes

---

Yes

---

Power Short-circuit Detection

---

Unconnected Line Detection

---

Load Short-circuit Detection

---

Disconnected Line Detection

---

Removable Terminal Block Structure

Yes

Expansion Using Expansion Units

---

Yes

---

Yes

---

Yes

Scaling

---

Last Maintenance Date

Yes

Cumulative Counter

---

Moving Average

---

Setting the Number of AD Conversion Points

---

Rate of Change

---

Comparator

---

Peak/Bottom Hold

---

Top/Valley Hold

---

User Adjustment

---

Top/Valley Count

---

Temperature Range Total Time Count

---

Input Temperature Variation Detection

---

Input Error Detection Disable Function

---

 

Note: The Contact Operation Monitor and the Total ON Time Monitor cannot be used at the same time for the same contact.

 

 

Yes: Supported, ---: Not supported

 

Function

Digital I/O Slave Units

3-tier Terminal block

CRT1-[]D08TA(-1)

CRT1-[]D08TAH(-1) *

CRT1-[]D16TA(-1)

CRT1-[]D16TAH(-1) *

Input Units

Output Units

Input Units

Output Units

Input Units

Output Units

I/O Units

Input Units

Output Units

I/O Units

Operation Time Monitor

Yes

Contact Operation Monitor (See note.)

Yes

Total ON Time Monitor (See note.)

Yes

Automatic Baud Rate Detection

Yes

Unit Conduction Time Monitor

Yes

Naming Units

Yes

Naming Connected Devices

Yes

Network Power Voltage Monitor

Yes

I/O Power Status Monitor

Yes

Communications Error History Monitor

Yes

Input Filter

Yes

---

Yes

---

Yes

---

Yes

Yes

---

Yes

Communications Error Output

---

Yes

---

Yes

---

Yes

Yes

---

Yes

Yes

Preventing Malfunctions Caused by Inrush Current at I/O Startup

Yes

---

Yes

---

Yes

---

Yes

Yes

---

Yes

Power Short-circuit Detection

---

Yes --- --- Yes --- Yes

Unconnected Line Detection

---

Yes --- --- Yes --- Yes

Load Short-circuit Detection

---

--- Yes --- --- Yes Yes

Disconnected Line Detection

---

--- Yes --- --- Yes Yes

Removable Terminal Block Structure

Yes

Expansion Using Expansion Units

---

Scaling

---

Last Maintenance Date

Yes

Cumulative Counter

---

Moving Average

---

Setting the Number of AD Conversion Points

---

Rate of Change

---

Comparator

---

Peak/Bottom Hold

---

Top/Valley Hold

---

User Adjustment

---

Top/Valley Count

---

Temperature Range Total Time Count

---

Input Temperature Variation Detection

---

Input Error Detection Disable Function

---

 

Note: The Contact Operation Monitor and the Total ON Time Monitor cannot be used at the same time for the same contact.

 

* With Short-circuit and Disconnected Line Detection

 

 

Yes: Supported, ---: Not supported

 

Function

Digital I/O Slave Units

Units with e-CON Connectors

CRT1-[]D16S(-1)

CRT1-[]D16SH(-1) *

CRT1-[]D32S(-1)

CRT1-[]D32SH(-1) *

Input Units

Output Units

I/O Units

Input Units

Output Units

I/O Units

Input Units

Output Units

I/O Units

Input Units

Output Units

I/O Units

Operation Time Monitor

Yes

Contact Operation Monitor (See note.)

Yes

Total ON Time Monitor (See note.)

Yes

Automatic Baud Rate Detection

Yes

Unit Conduction Time Monitor

Yes

Naming Units

Yes

Naming Connected Devices

Yes

Network Power Voltage Monitor

Yes

I/O Power Status Monitor

---

Yes

Yes

---

Yes

Yes

---

Yes

Yes

---

Yes

Yes

Communications Error History Monitor

Yes

Input Filter

Yes

---

Yes

Yes

---

Yes

Yes

---

Yes

Yes

---

Yes

Communications Error Output

---

Yes

Yes

---

Yes

Yes

---

Yes

Yes

---

Yes

Yes

Preventing Malfunctions Caused by Inrush Current at I/O Startup

Yes

---

Yes

Yes

---

Yes

Yes

---

Yes

Yes

---

Yes

Power Short-circuit Detection

---

Yes --- Yes --- Yes --- Yes

Unconnected Line Detection

---

Yes --- Yes --- Yes --- Yes

Load Short-circuit Detection

---

--- Yes Yes --- --- Yes Yes

Disconnected Line Detection

---

--- Yes Yes --- --- Yes Yes

Removable Terminal Block Structure

---

Expansion Using Expansion Units

---

Scaling

---

Last Maintenance Date

Yes

Cumulative Counter

---

Moving Average

---

Setting the Number of AD Conversion Points

---

Rate of Change

---

Comparator

---

Peak/Bottom Hold

---

Top/Valley Hold

---

User Adjustment

---

Top/Valley Count

---

Temperature Range Total Time Count

---

Input Temperature Variation Detection

---

Input Error Detection Disable Function

---

 

Note: The Contact Operation Monitor and the Total ON Time Monitor cannot be used at the same time for the same contact.

 

* With Short-circuit and Disconnected Line Detection

 

 

Yes: Supported, ---: Not supported

 

Function

Digital I/O Slave Units

Units with e-CON Connectors

Units with MIL Connectors

CRT1-V[]D08S(-1)

CRT1-V[]D16ML(-1)

CRT1-V[]D32ML(-1)

Input Units

Output Units

Input Units

Output Units

Input Units

Output Units

I/O Units

Operation Time Monitor

Yes

Contact Operation Monitor (See note.)

Yes

Total ON Time Monitor (See note.)

Yes

Automatic Baud Rate Detection

Yes

Unit Conduction Time Monitor

Yes

Naming Units

Yes

Naming Connected Devices

Yes

Network Power Voltage Monitor

Yes

I/O Power Status Monitor

---

Yes Yes

Communications Error History Monitor

Yes

Input Filter

Yes

---

Yes

---

Yes

---

Yes

Communications Error Output

---

Yes

---

Yes

---

Yes

Yes

Preventing Malfunctions Caused by Inrush Current at I/O Startup

Yes

---

Yes

---

Yes

---

Yes

Power Short-circuit Detection

---

Unconnected Line Detection

---

Load Short-circuit Detection

---

Disconnected Line Detection

---

Removable Terminal Block Structure

---

Expansion Using Expansion Units

---

Scaling

---

Last Maintenance Date

Yes

Cumulative Counter

---

Moving Average

---

Setting the Number of AD Conversion Points

---

Rate of Change

---

Comparator

---

Peak/Bottom Hold

---

Top/Valley Hold

---

User Adjustment

---

Top/Valley Count

---

Temperature Range Total Time Count

---

Input Temperature Variation Detection

---

Input Error Detection Disable Function

---

 

Note: The Contact Operation Monitor and the Total ON Time Monitor cannot be used at the same time for the same contact.

 

 

Yes: Supported, ---: Not supported

 

Function

Digital I/O Slave Units

Units with Screw-less Clamp Terminals

CRT1-[]D08SL(-1) CRT1-[]D16SL(-1)

Input Units

Output Units

Input Units

Output Units

I/O Units

Operation Time Monitor

Yes

Contact Operation Monitor (See note.)

Yes

Total ON Time Monitor (See note.)

Yes

Automatic Baud Rate Detection

Yes

Unit Conduction Time Monitor

Yes

Naming Units

Yes

Naming Connected Devices

Yes

Network Power Voltage Monitor

Yes

I/O Power Status Monitor

Yes

Communications Error History Monitor

Yes

Input Filter

Yes

---

Yes

---

Yes

Communications Error Output

---

Yes

---

Yes

Yes

Preventing Malfunctions Caused by Inrush Current at I/O Startup

Yes

---

Yes

---

Yes

Power Short-circuit Detection

---

Unconnected Line Detection

---

Load Short-circuit Detection

---

Disconnected Line Detection

---

Removable Terminal Block Structure

Yes

Expansion Using Expansion Units

---

Scaling

---

Last Maintenance Date

Yes

Cumulative Counter

---

Moving Average

---

Setting the Number of AD Conversion Points

---

Rate of Change

---

Comparator

---

Peak/Bottom Hold

---

Top/Valley Hold

---

User Adjustment

---

Top/Valley Count

---

Temperature Range Total Time Count

---

Input Temperature Variation Detection

---

Input Error Detection Disable Function

---

 

Note: The Contact Operation Monitor and the Total ON Time Monitor cannot be used at the same time for the same contact.

 

 

Yes: Supported, ---: Not supported

 

Function

Analog I/O Slave Units

2-tier Terminal block

Units with e-CON Connectors

Units with MIL Connectors

CRT1-AD04

CRT1-DA02

CRT1-VAD04S

CRT1-VDA02S

CRT1-VAD04ML

CRT1-VDA02ML

Input Units

Output Units

Input Units

Output Units

Input Units

Output Units

Operation Time Monitor

---

Contact Operation Monitor (See note.)

---

Total ON Time Monitor (See note.)

---

Automatic Baud Rate Detection

Yes

Unit Conduction Time Monitor

Yes

Naming Units

Yes

Naming Connected Devices

Yes

Network Power Voltage Monitor

Yes

I/O Power Status Monitor

---

Communications Error History Monitor

Yes

Input Filter

---

Communications Error Output

---

Yes

---

Yes

---

Yes

Preventing Malfunctions Caused by Inrush Current at I/O Startup

---

Power Short-circuit Detection

---

Unconnected Line Detection

---

Load Short-circuit Detection

---

Disconnected Line Detection

Yes

--- Yes --- Yes ---

Removable Terminal Block Structure

Yes

Expansion Using Expansion Units

---

Scaling

Yes

Last Maintenance Date

Yes

Cumulative Counter

Yes

Moving Average

Yes

---

Yes

---

Yes

---

Setting the Number of AD Conversion Points

Yes

---

Yes

---

Yes

---

Rate of Change

Yes

---

Yes

---

Yes

---

Comparator

Yes

---

Yes

---

Yes

---

Peak/Bottom Hold

Yes

---

Yes

---

Yes

---

Top/Valley Hold

Yes

---

Yes

---

Yes

---

User Adjustment

Yes

Top/Valley Count

---

Temperature Range Total Time Count

---

Input Temperature Variation Detection

---

Input Error Detection Disable Function

---

 

Note: The Contact Operation Monitor and the Total ON Time Monitor cannot be used at the same time for the same contact.

 

 

Yes: Supported, ---: Not supported

 

Function

Analog I/O Slave Units (Numerical indicator type)

Temperature Input Units

Units with e-CON Connectors Units with MIL Connectors

CRT1-TS04T

CRT1-TS04P

CRT1-VAD02SD
CRT1-VDA02SD

CRT1-VAD02MLD
CRT1-VDA02MLD

Input Units

Output Units

Input Units

Output Units

Input Units

Operation Time Monitor

---

---

Contact Operation Monitor (See note.)

---

---

Total ON Time Monitor (See note.)

---

---

Automatic Baud Rate Detection

Yes

Yes

Unit Conduction Time Monitor

Yes

Yes

Naming Units

Yes

Yes

Naming Connected Devices

Yes

Yes

Network Power Voltage Monitor

Yes

Yes

I/O Power Status Monitor

---

---

Communications Error History Monitor

Yes

Yes

Input Filter

---

---

Communications Error Output

---

Yes

---

Yes

---

Preventing Malfunctions Caused by Inrush Current at I/O Startup

---

---

Power Short-circuit Detection

---

---

Unconnected Line Detection

---

---

Load Short-circuit Detection

---

---

Disconnected Line Detection

Yes --- Yes ---

Yes

Removable Terminal Block Structure

Yes

Yes

Expansion Using Expansion Units

---

---

Scaling

Yes

Yes

Last Maintenance Date

Yes

Yes

Cumulative Count

Yes

Yes

Moving Average

Yes --- Yes ---

Yes

Setting the Number of AD Conversion Points

Yes --- Yes ---

---

Rate of Change

Yes --- Yes ---

Yes

Comparator

Yes --- Yes ---

Yes

Peak/Bottom Hold

Yes --- Yes ---

Yes

Top/Valley Hold

Yes --- Yes ---

Yes

User Adjustment

Yes

Yes

Top/Valley Count

---

Yes

Temperature Range Total Time Count

---

Yes

Input Temperature Variation Detection

---

Yes

Input Error Detection Disable Function

---

Yes

 

Note: The Contact Operation Monitor and the Total ON Time Monitor cannot be used at the same time for the same contact.

 

 

Yes: Supported, ---: Not supported

 

Function

Bit Slave Units Bit Slaves with Compact Connectors Repeater Unit
CRT1B-[]D02S(-1) CRT1B-[]D02JS(-1) CRT1B-[]D04JS(-1) CRS1-RPT01

Input Units

Output Units

Input Units

Output Units

I/O Units

Input Units

Output Units

I/O Units

Operation Time Monitor

Yes

---

---

---

Contact Operation Monitor (See note.)

Yes

---

---

---

Total ON Time Monitor (See note.)

Yes

---

---

---

Automatic Baud Rate Detection

Yes Yes Yes Yes

Unit Conduction Time Monitor

Yes

---

---

Yes

Naming Units

Yes

---

---

Yes

Naming Connected Devices

Yes

---

---

---

Network Power Voltage Monitor

Yes

---

---

Yes

I/O Power Status Monitor

---

---

---

---

Communications Error History Monitor

Yes

---

---

Yes

Input Filter

Yes

---

Yes

---

Yes

Yes

---

Yes

---

Communications Error Output

---

Yes

---

Yes

Yes

---

Yes

Yes

---

Preventing Malfunctions Caused by Inrush Current at I/O Startup

Yes

---

--- ---

---

Power Short-circuit Detection

Yes --- --- --- ---

Unconnected Line Detection

--- --- --- ---

Load Short-circuit Detection

--- Yes --- --- ---

Disconnected Line Detection

--- --- ---

---

Removable Terminal Block Structure

--- --- ---

---

Expansion Using Expansion Units

--- --- ---

---

Scaling

--- --- ---

---

Last Maintenance Date

Yes --- ---

Yes

Cumulative Count

--- --- ---

---

Moving Average

--- --- ---

---

Setting the Number of AD Conversion Points

--- --- ---

---

Rate of Change

--- --- ---

---

Comparator

--- --- ---

---

Peak/Bottom Hold

--- --- ---

---

Top/Valley Hold

--- --- ---

---

User Adjustment

--- --- ---

---

Top/Valley Count

--- --- --- ---

Temperature Range Total Time Count

--- --- --- ---

Input Temperature Variation Detection

--- --- --- ---

Input Error Detection Disable Function

--- --- --- ---

 

Note: The Contact Operation Monitor and the Total ON Time Monitor cannot be used at the same time for the same contact.

 

 

    

Back