DNV Certification (Norwegian Marine Standards)
Programmable Controllers
|
Model |
Location Class |
|
Temperature |
Humidity |
Vibration |
EMC |
Enclosure |
|
C200HW/C200HX/C200HG/C200HE |
A |
A |
A |
A |
*3 |
|
CJ1/CJ2 |
A |
B |
A |
A |
*3 |
|
CP1 |
B |
B |
A |
A*2 |
*3 |
|
CQM1H/CQM1 |
B |
A |
A |
A |
*3 |
|
CS1 |
B |
B |
A |
A |
*3 |
|
CVM1D /CV500/C500/C1000H |
B*1 |
B*1 |
A |
A |
*3 |
*1. The C1000H-APS01, however, is "A."
*2. Install inside a metal enclosure.
*3. There are no enclosure requirements for OMRON products. Follow the DNV
enclosure requirements specified separately for installation locations of the
panel containing the product.
Note 1: The above table lists series names. Ask your OMRON representative for
details on specific model numbers.
Note 2: Model certification has not been received for usage on the deck, in the
bridge, or in locations subject to strong vibration.
Model certification for the DNV (Det Norske Veritas) was made according to the
Environmental Test Specific for Instrument and Automation Equipment Standard for
Certification No. 2.4.
Refer
to the following table for the location classes.
|
Column I |
Column II |
|
Parameter |
Location within main area |
MAIN AREAS ON BOARD |
|
Machinery spaces |
Control room, Accommodation |
Bridge |
Pump room, Holds, Rooms with no heating |
Open Deck |
|
Temperature |
Inside cubicles, desks, etc. with temperature rise
of 5°C or more |
B |
B |
B |
D |
D |
|
All other locations |
A |
A |
A |
C |
D |
|
Humidity |
Locations where special precautions are taken to
avoid condensation |
A |
A |
A |
A |
A |
|
All other locations |
B |
B |
B |
B |
B |
|
Vibration |
On machinery such as internal combustion engines,
compressors, pumps, including piping on such machinery |
B |
--- |
--- |
B |
B |
|
Masts |
--- |
--- |
--- |
--- |
C |
|
All other locations |
A |
A |
A |
A |
A |
|
EMC |
All locations within specified main |
A |
A |
B |
A |
B |
|
Enclosure |
Submerged application |
D |
--- |
--- |
D |
D |
|
Below floor plates in engine room |
C |
--- |
-- |
--- |
--- |
|
All other locations |
B |
A |
A |
B |
C |
Field
Networks
* There are no enclosure requirements for OMRON products. Follow the DNV
enclosure requirements specified separately for installation locations of the
panel containing the product.
Note 1: The above table lists series names. Ask your OMRON representative for
details on specific model numbers.
Note 2: Model certification has not been received for usage on the deck, in the
bridge, or in locations subject to strong vibration.
Programmable
Terminals
|
Model |
Location Class |
Temperature |
Humidity |
Vibration |
EMC |
Enclosure |
|
NS5/NS8/NS10/NS12 |
A |
B |
A |
B |
A |
Note:
1. The
above table lists series names. Ask your OMRON representative for details on
specific model numbers.
2. Model certification has not been received for usage on the deck, in the
bridge, or in locations subject to strong vibration.
Reduced
Wiring Devices
|
Model |
Location Class |
|
Temperature |
Humidity |
Vibration |
EMC |
Enclosure |
|
G71/G72C |
B |
B |
A |
A |
* |
* There
are no enclosure requirements for OMRON products. Follow the DNV enclosure
requirements specified separately for installation locations of the panel
containing the product.
Note:
1. The
above table lists series names. Ask your OMRON representative for details on
specific model numbers.
2. Model certification has not been received for usage on the deck, in the
bridge, or in locations subject to strong vibration.
The following DNV (Det Norske Veritas) rules apply: Environmental Test Specific
for Instrument and Automation Equipment Standard for Certification No. 2.4.
|