Alternate Operation Relay
last update: April 1, 2022
| 61F-AO-CP08-NRA | |
|---|---|
| Supply voltage/frequency | 100 VAC - 240 VAC 50/60 Hz |
| Operating voltage range | 85 to 110% of rated voltage |
| Operating frequency range | ± 5 Hz of the rated frequency |
| Power consumption | 1.6 VA max. |
| Contact ratings | 3 A at 250 VAC (Resistive load (cosφ = 1))
1.5 A at 250 VAC (Inductive load (cosφ = 0.4)) |
| Ambient temperature | -10 to 55°C |
| Ambient humidity | 25% to 85% RH |
| Ambient storage temperature | -10 to 55°C |
| Ambient storage humidity | 25% to 85% RH |
| Weight | Approx. 100 g |
| Accessories | PFC-N8 |
| 61F-AO-CP08-NRA | |
|---|---|
| Response time | Operate: 25 ms max.
Release: 30 ms max. |
| Minimum pulse width | Min. ON time: 40 ms min.
Min. OFF time: 2 s min. |
| Insulation resistance | 10 MΩ min. at 500 VDC
(between each terminal and power supply) |
| Dielectric strength | 2,000 VAC, 50/60 Hz for 1 min
(between each terminal and power supply) |
| Life expectancy | Electrical: 100,000 operations min.
Mechanical: 1,000,000 operations min. |
last update: April 1, 2022