Page top

Industrial Automation

Industrial Automation

Discontinued On Mar. 2015

E2EV

All Metal Proximity Sensor

E2EV

Long-distance Detection of Both Ferrous of Non-ferrous Metals

* Information in this page is a reference that you created on the basis of information in the product catalog before the end of production, may be different from the current situation, such as goods for / supported standards options / price / features of the product. Before using, please check the compatibility and safety system.

Model E2EV-X2C1
E2EV-X2C2
E2EV-X5C1
E2EV-X5C2
E2EV-X10C1
E2EV-X10C2
Sensing distance 2mm ±10% 5 mm ±10% 10 mm ±10%
Set distance 0 to 1.4 mm 0 to 3.5 mm 0 to 7 mm
Differential travel 10% max. of sensing distance
Detectable object Ferrous metal and non-ferrous metal
Standard sensing object Aluminum: 12 × 12 × 1 mm Aluminum: 18 × 18 × 1 mm Aluminum: 30 × 30 × 1 mm
Response frequency * 150 Hz 70 Hz
Power supply voltage
(operating voltage range)
12 to 24 VDC (10 to 30 VDC), ripple (p-p): 10% max.
Current consumption 15 mA max.
Control
output
Load
current
NPN open-collector output, 100 mA max. (at 30 VDC)
Residual
voltage
2 V max. (Load current: 100 mA, Cable length: 2 m)
Indicators Detection indicator (red)
Operation mode
(with sensing object approaching)
C1 Models: NO
C2 Models: NC
Refer to Datasheet.
Protection circuits Reverse polarity protection, Load short-circuit protection, Surge suppressor
Ambient temperature range Operating/Storage: -10 to 55°C (with no icing or condensation)
Ambient humidity range Operating/Storage: 35% to 95% (with no condensation)
Temperature influence ±20% max. of sensing distance at 23°C in the temperature range of -10 to 55°C
Voltage influence ±2.5% max. of sensing distance at rated voltage in the rated voltage ±15% range
Insulation resistance 50 MΩ min. (at 500 VDC) between current-carrying parts and case
Dielectric strength 1,000 VAC, 50/60 Hz for 1 minute between current-carrying parts and case
Vibration resistance Destruction: 10 to 55 Hz, 1.5-mm double amplitude for 2 hours each in X, Y, and Z directions
Shock resistance Destruction: 1,000 m/s2 10 times each in X, Y, and Z directions
Degree of protection IEC 60529 IP67, in-house standards: oil-resistant
Connection method Pre-wired Models (Standard cable length: 2 m)
Weight (packed state) Approx. 120 g Approx. 140 g Approx. 190 g
Materials Case Nickel-plated brass
Sensing
surface
Heat-resistant ABS
Clamping
nuts
Nickel-plated brass
Toothed
washer
Zinc-plated iron
Accessories Instruction manual

* The response frequency is an average value. Measurement conditions are as follows: standard sensing object, a
  distance of twice the standard sensing object, and a set distance for the DC switching section of half the sensing
  distance.